Abstract
This paper presents a mathematical model to enable a more in-depth understanding of the combined heat and mass transfer processes of a counter-flow indirect evaporative cooler operating in semi-arid regions. A series of simulation was conducted to compare the performances between a single-purge and four-purge configurations. Furthermore, the effect of several parameters on the performance of the single-purge configuration was investigated under the baseline condition. The developed model was validated against experimental data from literature to within 2% discrepancy. Key results revealed that the single-purge configuration produced higher cooling capacity (around 20% higher), as well as higher dew-point effectiveness under the same operating conditions. A parametric study was also made on the single-purge configuration. The results revealed that lower product air temperature and higher dew-point effectiveness were achieved with longer channel length and larger purge ratio. However, the maximum cooling capacity approached its maximum with longer channel length and 35% purge ratio.
| Original language | English |
|---|---|
| Pages (from-to) | 505-515 |
| Number of pages | 11 |
| Journal | Energy |
| Volume | 168 |
| Early online date | 21 Nov 2018 |
| DOIs | |
| Publication status | Published - 1 Feb 2019 |
| Externally published | Yes |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Cooling capacity
- Dew-point evaporative cooler
- Indirect evaporative cooler
- Numerical simulation
- Purge configuration
Fingerprint
Dive into the research topics of 'Approaches to energy efficiency in air conditioning: A comparative study on purge configurations for indirect evaporative cooling'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver